Ser |
Description |
Remarks |
a. |
Type |
Universal |
b. |
Model/Brand |
To be mentioned |
c. |
Drive |
It should have a 5-7 kW
electric motor, controlled by a frequency controller. Drive shaft and base
adaptors should be compatible with any governor (Woodward, Regulator Europa
& YT555G). |
d. |
Power supply |
Voltage: 440± 5%, 3Ph, 50 Hz. |
e. |
Operation Mode |
Open & close loop system. |
f. |
Control system |
PLC/microcontroller-based |
g・ |
Display |
ColourTouch screen HMI showing: a.
Speed b.
Governor output
position c.
Oil pressure d.
Solenoid voltage e.
Speed setting air
pressure f.
Actuator current g.
Drive speed |
|
Ser |
Description |
Remarks |
|
|
h. Governor output
shaft position j. Speed setting air pressure, accuracy 0.05 bar k. mA
command and feedback signal to final driver I. Fuel limit pressure, accuracy 0.05 bar m. Governor oil
pressure, accuracy 0.1 bar n. Governor oil temperature (when circulating) p.
Voltage stop or start fuel limit solenoid supply q. Voltage variable supply
r. Voltage at voltmeter input s. Actuator current |
h. |
Governor Drive speed |
100 -2,000 rpm |
j- |
Governor Oil system |
The test bench must
have to be a motor-driven oil pump, immersion heater and filter Capacity of
the oil tank of about 30-32 litres. Oil pressure adjustable from 5-10 bars. |
k. |
Pneumatic system |
Provision of 8-9 bar
air supply for the following settings: a.
Speed signal setting b.
Boost fuel limit
signal c.
Start booster test |
1. |
Electrical equipment
and functions |
a.
Operation of 24V DC
series wound speed setting motor b.
Operation of 24V DC PM
type speed setting motor c.
Operation of 115 /
230V AC series wound speed setting motor d.
Operation of RE
(Regulator Europa) 4-20 mA speed setting device e.
Operation of Woodward
4-20 mA speed setting device f.
Variable supply (0-24V
DC) for stopping and starting fuel limit solenoids g.
Operation of 115/230V
AC operated solenoids h.
Variable supply 0- 24V
DC j.
4 mm sockets must be
available k.
Magnet charger for
setting up actuators l.
Variable current
source fortesting actuators |
m. |
Operation |
Suitable colour touch screen along with sufficient
potentiometers and illuminated push buttons. Set points for pressure,
temperature, drive speed, load, etc, need to be entered as a digital value or
set using the set point potentiometer. |
n. |
Instrumentation |
The test bench must have analogue pressure gauges for speed
setting, pressure, fuel limit pressure, governor oil pressure and oil
pressure from load control device. |
|
Ser |
Description |
Remarks |
P- |
Output signal |
The test bench must have
two 0-10V DC signals representing speed and governor output for external
measurement. |
q. |
Weight |
To be mentioned |
r. |
Dimension |
To be mentioned |